Circuit breaker (5A) W/approval
UL : 3-30A 125V/250V
CSA: 3-30A 125V/5-30A 250V
VDE: 4-30A 250V
Unit price (USD)
Quantity Price
500+ 1.7212
Add
Enter Quantity to Check Lead Time
Data Sheet
Electrical Characteristics

Specifications

·Input power: 50VDC / 125VAC / 250VAC
·Current rated: 5A
·Insulation resistance: 100MΩ Min.
·Dielectric strength: 1500VAC for 1 minute
·Calibration:
25°C-100% of rated current-continuously carried
25°C-between 101% and 145%-may trip or not
25°C-150% of rated current-trip within 1 hour
25°C-200% of rated current-trip within 1 minute
·Contact endurance: 125VAC x 200% of rated current 500 cycles
·Reset: manual push reset
Trip time
Overload(5A ~ 40A)
600% 0.6 - 1.7 sec
500% 0.8 - 2.5 sec
400% 1.6 - 7.0 sec
300% 2.5 - 11 sec
200% 4.0 - 30 sec
150% trip within 1 hr
100% no trip
35A-40A trip within 1 min. at 200%